TABLE 1:
Source Table - Schedule of Essential safety measures |
|
|
Table I1.1 |
|
ESSENTIAL
SAFETY MEASURES - BUILDING FIRE INTEGRITY |
Essential
safety measure |
Definition |
Building
elements required to satisfy prescribed fire resistance levels |
To maintain structural stability during a fire and restrict the
spread of fire. It must be provided with the fire resistance level
specified in the BCA and have all openings protected with doors,
windows, shutters, panels or other means rated to provide the required
fire resistance level. |
Materials and
assemblies required to satisfy prescribed fire hazard properties |
Indicates the suitability or otherwise, of building materials,
etc. in the ability to resist spread of flame and the generation of
smoke. Building owners must ensure that any new material introduced to
their premises conforms to the requirements of the Building Code of
Australia. |
Elements
required to be non-combustible, provide fire protection,
compartmentation or separation |
To provide fire resistance wall, covering, etc that are built
into the structure during construction. |
Wall-wetting
sprinklers (including doors and windows required in conjunction
with wall-wetting sprinklers) |
To provide
protecting a non fire rated opening in a required fire resisting
element with the required fire protection. |
Fire doors
(including sliding fire doors and their associated warning
systems) and associated self-closing, automatic closing and
latching mechanisms |
The fire door must close upon the loss of power supply or due to
an approved sensing device (e.g heat detectors / fire alarm / sprinkler
system) and must close cleanly without impairment in its operation.
NO UNAUTHORISED means should be used to hold the door
open. |
Fire windows
(including windows that are automatic or permanently fixed in
the closed position) |
A glazed
opening provided with a fire rating in a fire rated wall to
maintain the fire resistance of the building element or
structure. |
Fire shutters |
Constructed and installed in compliance to the regulations, they
must operate automatically and close at a rate between 0.25 and 0.3
metres per second and maintain their integrity for the time period as
required by BCA.
|
Solid core
doors and associated self-closing, automatic closing and
latching mechanisms |
Provided in
certain circumstances to provide some level of resistance to the
spread of fire and smoke and has much the same requirements as a
fire door. |
Fire-protection at service penetrations through elements
required to be fire-resisting with respect to integrity or
insulation, or to have a resistance to the incipient spread of
fire |
Service penetrations into fire rate structures are to be
maintained to keep the integrity of its fire resistant level.
|
Fire
protection associated with construction joints, spaces and the
like in and between building elements required to be
fire-resisting with respect to integrity and insulation |
Assist in keeping the integrity and protection of structural
elements and fire/smoke resistant elements in the event of fire.
|
Smoke doors
and associated self-closing, automatic closing and latching
mechanisms |
Constructed in smoke walls to restrict the passage of smoke
between smoke compartments or walls, or from within a smoke lobby (i.e
from passing from one side of the doorway to the other). |
Proscenium
walls (Fire Curtains) |
Capable of closing automatically (heat activated device) fully
within 35 seconds or manually from either stage side to prevent the
passage of smoke and fire from the stage area to the audience area.
Non-combustible, inhibiting smoke penetration around its perimeter when
fully lowered or with specified early fire hazard indices and protection
by a deluge sprinkler system across its total width. |
|
|
Table I1.2 |
|
ESSENTIAL
SAFETY MEASURES - MEANS OF EGRESS |
Essential
safety measure |
Definition |
Paths of
travel to exits |
To provide an unobstructed pathway for occupants traveling to an
exit. The passage to an exit has to be the width and height as specified
by the Building Code of Australia.
|
Discharge
from exits (including paths of travel from open spaces to the
public roads to which they are connected) |
To provide an unobstructed pathway for occupants traveling from an
exit to road or open space. The path to road or open space has to be the width and height as specified
by the Building Code of Australia.
|
Exits
(including fire-isolated stairways and ramps, non-fire isolated
stairways and ramps, stair treads, balustrades and handrails
associated with exits, and fir-isolated passageways) |
To enable safe exit from the building for residents/staff (fire
doors are to be at entrance/exit points to these elements). These have
to be fire resistant at the level specified in the Building Code of
Australia. |
Smoke lobbies
to fire-isolated exits |
To provide fire resistance wall, covering, etc that are built
into the structure during construction to avoid the travel of smoke into
the exit paths. |
Open access
ramps or balconies for fire-isolated exits |
|
Doors (other
than fire or smoke doors) in a required exit, forming part of a
required exit or in a path of travel to a required exit, and
associated self-closing, automatic closing and latching
mechanisms |
To enable safe exit from the building. With minimum obstruction
in an exit path and the exit door to be opened in a single downward/push
action. |
|
|
Table I1.3 |
|
ESSENTIAL
SAFETY MEASURES - SIGNS |
|
Essential
safety measure |
Definition |
Exit signs
(including direction signs) |
To assist the residents/staff in identifying exits and paths of
travel to exits. It must be clearly visible (in adequate size letters
and symbols) to the person approaching an exit. It should be located in
positions where exits are not readily visible, on/above/adjacent to each
door providing exit and has emergency illumination in the event of
normal power supply failure. |
Signs
warning against the use of lifts in the event of fire |
Warning
signs, etc that warn users of using the lifts (passenger) in the
event of a fire.
|
Warning signs
on sliding fire doors and doors to non-required stairways, ramps
and escalators |
Warning
signs, etc that warn occupants that it is not the exit path in
the event of a fire.
|
Signs,
intercommunication systems, or alarm systems on doors of
fire-isolated exits stating that re-entry to storey is available |
Warning
signs, etc that warn occupants
within a fire isolated stair on how to
re-enter a particular level. |
Signs
alerting persons that the operation of doors must not be
impaired |
Warning
signs, etc that warn occupants
that they must not obstruct or impair the
function of a required door. |
Signs
required on doors, in alpine areas, alerting people that they
open inwards |
Warning
signs, etc that warn occupants that
the external exit doors open inwards to
avoid exit doors not being able to be opened by snow fall on the
out side of the door. |
Fire order
notices required in alpine areas |
Warning
signs, etc that warn occupants the
operation of fire alarms, fire fighting equipment, location of
exits and evacuation procedures. |
|
|
Table I1.4 |
|
ESSENTIAL
SAFETY MEASURES - LIGHTING |
|
Essential
safety measure |
Definition |
Emergency
lighting |
To provide sufficient lighting to allow safe evacuation in an
event of an emergency. It must at least illuminate in the event of power
failure and enough light in regards to the distance to the exits, use
and size in the floor area of the building. |
|
|
Table I1.5
|
|
ESSENTIAL
SAFETY MEASURES - FIRE FIGHTING SERVICES AND EQUIPMENT |
Essential
safety measure |
Definition |
Fire hydrant
system (including on-site pump set and fire-service booster
connection) |
This is to provide the fire fighting personnel a supply of water,
which is readily accessible and located to provide coverage and a
specified minimum flow rate (at all times) to every part of the
building. |
Fire hose reel
system |
To enable the residents/staff to undertake initial fire
extinguishment. The hose reel length must be to reach every part of the
floor or storey on which it is installed. The location of the hose has
to be clearly indicated and instructions on how to operate it, displayed
on the hose reel. Staff and personnel are required to be trained in the
usage of the hose reels. |
Sprinkler
system |
A full-time automatic fire suppression system that is able to
summon the fire brigade automatically. |
Portable fire
extinguishers |
To enable the residents/staff to attack a fire in its initial
stages, with the suitable agents for the likely type of fire. The fire
extinguishers must be located in conspicuous and in an accessible
position, which are indicated by the appropriate signage. Staff and
personnel must be suitably trained in the correct use of fire
extinguishers located in the premises. |
Fire control
centres (or rooms) |
It is the centre from which fire fighting operations or emergency
procedures are directed or controlled. Equipments associated with
required fire services in the building, and are only used for fire
fighting and for the safety or security of the residents/staff. |
Provisions for
special hazards |
|
|
|
Table I1.6 |
|
ESSENTIAL
SAFETY MEASURES - AIR HANDLING SYSTEMS |
Essential
safety measure |
Definition |
Smoke hazard
management systems:
• automatic
air pressurisation systems for fire- isolated exits
• zone smoke
control system
• smoke
exhaust system automatic smoke and heat vents (including
automatic vents for atriums)
• air
handling systems that do not form part of a smoke hazard
management system and which may unduly contribute to the spread
of smoke
•
miscellaneous air- handling systems covered by Sections 5 and 11
of AS/NZS1668.1 serving more than one fire compartment |
To provide sufficient time for residents/staff to evacuate before
the evacuation route becomes untenable. The purpose is to remove smoke
from fire affected area to the outside area and introduce outside air to
either fire affected area or non fire affected compartments, in response
to the heat or smoke sensing equipment and provide a pressurised
atmosphere in fire isolated exits to prevent entry of smoke from the
fire compartment. |
Carpark
mechanical ventilation system |
|
Atrium smoke
control system (see above for smoke and heat vents) |
|
|
|
Table I1.7 |
|
ESSENTIAL
SAFETY MEASURES - AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS |
Essential
safety measure |
Definition |
Smoke and
heat alarm system |
To detect and provide an early warning of the presence of fire,
providing as much time as possible to alert the residents/staff. |
Smoke and
heat detection system |
To automatically sense the fire in its initial development stage
and provide a local alarm and advise the fire brigade and indicate the
location of the fire (also has manual means to activate the system) and
switch the air handling system to the smoke ventilating phase and
activate necessary fire pumps and the closure of smoke and fire
isolating doors. |
Atrium fire
detection and alarm systems |
|
|
Table I1.8 |
|
ESSENTIAL
SAFETY MEASURES - OCCUPANT WARNING SYSTEMS |
Essential
safety measure |
Definition |
Emergency
warning and intercommunication system |
To alert the residents/staff in the event of an emergency and
enable an orderly evacuation of the building. Staff and personnel are
required to be trained in identification of the "alert" and "evacuation"
signals (audio or visual), and take part in an evacuation exercises. |
Building
occupant warning system |
|
|
Table I1.9 |
|
ESSENTIAL
SAFETY MEASURES - LIFTS |
|
Essential
safety measure |
Definition |
Stretcher
facilities in lifts |
Allows the emergency services personnel to use stretcher facilities in a lift. |
Emergency
lifts |
Allows the emergency services personnel to gain entry to any
floor of the building and proceed in the evacuation of staff and
residents and carry out emergency procedures. |
Passenger
lift fire service controls |
|
|
Table
I1.10 |
|
ESSENTIAL
SAFETY MEASURES - STANDBY POWER SUPPLY SYSTEMS |
Essential
safety measure |
Definition |
Standby power
supply system |
In the event of a power failure, an emergency power supply will
ensure the operation of the safety systems. In terms of a generating
set, it is required to provide power within 30 seconds of mains failure. |
|
|
Table
I1.11 |
|
ESSENTIAL
SAFETY MEASURES - BUILDING CLEARANCE AND FIRE APPLIANCES |
Essential
safety measure |
Definition |
Open space
around large isolated buildings |
For buildings constructed in excess of the floor area
requirements of the BCA, vehicular access around that building for
emergency services from a public road is required. The road has to be
load bearing capability with unobstructed height and a min. width of 6
metres and no part of it further than 18 metres from the building. |
Vehicular
access around large isolated buildings |
|
|
I1.2 |
|
ESSENTIAL
SAFETY MEASURES - MECHANICAL VENTILATION |
Essential
safety measure |
Definition |
Air
conditioning systems |
Safeguards residents/staff from illness or loss of amenity due to
lack of air freshness e.g. kitchen exhaust, air condition, evaporative
cooling, general exhaust, thermal plants, humidifiers, electric duct
heaters, etc. |
|
|