Welcome to the Website of :
 

 

 

 

 

Home
About UsBuilding ServicesEssential Safety MeasuresESM TablesESM DefinitionsESM Links and InformationBenchmarking TodayForms
LinksContact Us

                                                                                           
 Essential Safety Measures

 

The essential safety measure tables have changes over time. The following lists help to explain what the difference is.

Table 1 - Post 2004 Essential Safety Measure List

Table 2 - 1994 -2004 Essential Safety Measure List

Table 3 - Comparison Between Tables 1 & 2

 

ESSENTIAL SAFETY MEASURE LIST AND REQUIREMENTS FOR BUILDINGS BUILT AFTER MAY 2004

 

TABLE 1: Source Table - Schedule of Essential safety measures

 

 

 

Table I1.1

 

 

ESSENTIAL SAFETY MEASURES - BUILDING FIRE INTEGRITY

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Building elements required to satisfy prescribed fire resistance levels

Section C, D1.12

Annual Inspection for damage, deterioration, or unauthorised alteration

Materials and assemblies required to satisfy prescribed fire hazard properties

C1.10

Annual Inspection for damage, deterioration, or unauthorised alteration

Elements required to be non-combustible, provide fire protection, compartmentation or separation

C2.5 to C2.14, C3.3, C3.11, D1.7 - D1.8, E1.3, G3.4

Annual Inspection for damage, deterioration, or unauthorised alteration

Wall-wetting sprinklers (including doors and windows required in conjunction with wall-wetting sprinklers)

C3.4, C3.8, C3.11, D1.7, D1.8, G3.8

As per AS 1851-2005 Section 2 if Sprinkler system installed or every six months to ensure compliance, no damage or deterioration  and water supply availability.

Fire doors (including sliding fire doors and their associated warning systems) and associated self-closing, automatic closing and latching mechanisms

C2.12 to C2.13, C3.4 to C3.8, C3.10 to C3.11, D1.7 to D1.8, D1.12

Every three months as per AS1851 - 2005 Section 17 check operation of handles, closers and electronic strikes

Fire windows (including windows that are automatic or permanently fixed in the closed position)

C3.4, C3.8, C3.11, D1.7 to D1.8

Every six months as per AS1851 - 2005 Section 17 for damage, deterioration, or unauthorised alteration, BCA (refer appendix E)

Fire shutters

C3.4 to C3.5, D1.7 to D1.8 AS 1905.2-1989

Every three months as per AS1851 - 2005 Section 17, Annual Inspection for damage, deterioration, or unauthorised alteration

Solid core doors and associated self-closing, automatic closing and latching mechanisms

C3.11

Annual Inspection for damage, deterioration, and check operation of closers, handles and electronic strikes.

Fire-protection at service penetrations through elements required to be fire-resisting with respect to integrity or insulation, or to have a resistance to the incipient spread of fire

C3.12, C3.13, C3.15

Every six months as per AS1851 - 2005 Inspection for damage, deterioration, or unauthorised alteration

Fire protection associated with construction joints, spaces and the like in and between building elements required to be fire-resisting with respect to integrity and insulation

C3.16

Every six months as per AS1851 - 2005 Inspection for damage, deterioration, or unauthorised alteration

Smoke doors and associated self-closing, automatic closing and latching mechanisms

Specification C2.5, D2.6

Every three months as per AS1851 - 2005. Check operation of closers, handles and electronic strikes

Proscenium walls (Fire Curtains)

H1.3

Annual Inspection for damage, deterioration or unauthorised alteration

  

 

 

Table I1.2

 

 

ESSENTIAL SAFETY MEASURES - MEANS OF EGRESS

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Paths of travel to exits

D1.6

Inspection every three months to ensure there are no obstructions and no alterations

Discharge from exits (including paths of travel from open spaces to the public roads to which they are connected)

D1.7, D1.9 to D1.11, D2.12, G4.3, G4.6, G4.7

Inspection every three months to ensure there are no obstructions and no alterations

Exits (including fire-isolated stairways and ramps, non-fire isolated stairways and ramps, stair treads, balustrades and handrails associated with exits, and fir-isolated passageways)

D2.2 to D2.3, D2.8 to D2.11inc., D2.13, D2.16 to D2.17

Inspection every three months to ensure there are no obstructions and no alterations

Smoke lobbies to fire-isolated exits

D1.7, D2.6

Annual inspection for damage, deterioration, or unauthorised alteration

Open access ramps or balconies for fire-isolated exits

D2.19 to D2.23

Annual inspection for damage, deterioration, or unauthorised alteration

Doors (other than fire or smoke doors) in a required exit, forming part of a required exit or in a path of travel to a required exit, and associated self-closing, automatic closing and latching mechanisms

D1.6, D2.19 to D2.21, D2.23

Inspection every three months to ensure doors are intact, operational and fitted with conforming hardware

 

 

 

Table I1.3

 

 

ESSENTIAL SAFETY MEASURES - SIGNS

 

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Exit signs (including direction signs)

D1.12, E4.5, E4.6, E4.8

Every six months to AS 2293.2-1995

Signs warning against the use of lifts in the event of fire

C3.6, D1.12

Annual inspection to ensure the warning sign is in place and legible

Warning signs on sliding fire doors and doors to non-required stairways, ramps and escalators

D2.2 to D2.3, D2.8 to D2.11inc., D2.13, D2.16 to D2.17

Annual inspection to ensure the warning sign is in place and legible

Signs, intercommunication systems, or alarm systems on doors of fire-isolated exits stating that re-entry to storey is available

D2.22

Annual inspection to ensure the warning sign is in place and legible

Signs alerting persons that the operation of doors must not be impaired

D2.23

Annual inspection to ensure the warning sign is in place and legible

Signs required on doors, in alpine areas, alerting people that they open inwards

G4.3

Annual inspection to ensure the warning sign is in place and legible

Fire order notices required in alpine areas

G4.9

Annual inspection to ensure the warning sign is in place and legible

 

 

 

Table I1.4

 

 

ESSENTIAL SAFETY MEASURES - LIGHTING

 

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Emergency lighting

E4.2, E4.4

Every six months to AS 2293.2-1995

 

 

 

Table I1.5

 

 

ESSENTIAL SAFETY MEASURES - FIRE FIGHTING SERVICES AND EQUIPMENT

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Fire hydrant system (including on-site pump set and fire-service booster connection)

E1.3

Weekly to AS 1851 - 2005 Section 4 where pumps are installed or six monthly to AS1851 -2005 Section 4

Fire hose reel system

E1.4

Every six months to AS 1851 - 2005 Section 14

Sprinkler system

E1.5, H1.2, G3.8

Weekly to AS 1851 - 2005 Section 21

Portable fire extinguishers

E1.6

Every six months to AS 1851 -2005 Section 15.4

Fire control centres (or rooms)

E1.8

Annual inspection to ensure compliance of construction and contents with BCA

Provisions for special hazards

E1.10

Inspection regime to be developed in consultation with designer utilising appropriate Australian standards, manufacturer specifications, etc.

 

 

 

Table I1.6

 

 

ESSENTIAL SAFETY MEASURES - AIR HANDLING SYSTEMS

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Smoke hazard management systems:

•   automatic air pressurisation systems for fire- isolated exits

•   zone smoke control system

•   smoke exhaust system automatic smoke and heat vents (including automatic vents for atriums)

•   air handling systems that do not form part of a smoke hazard management system and which may unduly contribute to the spread of smoke

•    miscellaneous air- handling systems covered by Sections 5 and 11 of AS/NZS1668.1 serving more than one fire compartment

E2.2

Quarterly and as prescribed in AS 1851 -2005 Section 18

Carpark mechanical ventilation system

F4.11

Frequency as nominated by manufacturer on label attached to equipment in accordance with AS1851 - 2005 Section 18

Atrium smoke control system (see above for smoke and heat vents)

Specification G3.8

As per AS1851 - 2005 Section 18

 

 

 

Table I1.7

 

 

ESSENTIAL SAFETY MEASURES - AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Smoke and heat alarm system

Clause 3 of Specification E2.2a

As prescribed in AS 1851 - 2005 Section 7 Monthly inspection to test operation Replace battery or unit as necessary

Smoke and heat detection system

Clause 4 of Specification E2.2a

Monthly as prescribed in AS1851 - 2005 Section 6

Atrium fire detection and alarm systems

Clause 4 of Specification G3.8(AS1670.1)

Monthly as prescribed in AS1851 - 2005 Section 6

  

 

 

Table I1.8

 

 

ESSENTIAL SAFETY MEASURES - OCCUPANT WARNING SYSTEMS

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Emergency warning and intercommunication system

E4.9 Clause 6 of Specification G3.8

Monthly to AS 1851 - 2005 Section 10

Building occupant warning system

Clause 8 of Specification E1.5, Clause 6 of Specification E2.2a

Monthly as prescribed AS 1851 - 2005 Section 9

 

 

 

Table I1.9

 

 

ESSENTIAL SAFETY MEASURES - LIFTS

 

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Stretcher facilities in lifts

E3.2

Annual inspection to ensure compliance of facilities with BCA

Emergency lifts

E3.4

As Per requirements of AS 1735 Periodic inspection as per manufacturers specification, however no less than annual inspection

Passenger lift fire service controls

E3.7

Periodic inspection as per manufacturers specification, however no less than annual inspection.

 

 

 

Table I1.10

 

 

ESSENTIAL SAFETY MEASURES - STANDBY POWER SUPPLY SYSTEMS

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Standby power supply system

E3.4, Clause 6 of Specification G3.8

Every six months test to ensure auxiliary power is operable. For diesel engines - test as prescribed in AS 1851 - 2005 based on proving electrical load in lieu of flow/pressure for pump sets

 

 

 

Table I1.11

 

 

ESSENTIAL SAFETY MEASURES - BUILDING CLEARANCE AND FIRE APPLIANCES

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Open space around large isolated buildings

C2.3 to C2.4

Annual inspection to ensure that unobstructed access to buildings and fire fighting facilities are maintained

Vehicular access around large isolated buildings

C2.3 to C2.4

Annual inspection to ensure clearance is maintained

 

 

 

I1.2

 

 

ESSENTIAL SAFETY MEASURES - MECHANICAL VENTILATION

Essential safety measure

BCA provisions

Nature and or frequency of test or inspection

Air conditioning systems

AS 1668.2-1991, BCA E2.2

Quarterly to AS 1851- 20051, AS 3666-1995

 

 

 

  

ESSENTIAL SAFETY MEASURE LIST FOR BUILDINGS BUILT BETWEEN JULY 1994 AND MAY 2004

The following source table has been reproduced to provide some level of guidance to practitioners having to deal with buildings constructed in period of July 1994 to May 2004.

 TABLE 2: Source Table - BCA 96 and BCA 90, Schedule of Essential safety measures 

Essential safety measure to be inspected or tested

Installation standards/ level of performance

Nature of inspection or test and Frequency of inspection or test2

Air conditioning systems

AS 1668.2-1991

Monthly to AS 1851.6-1983 or Monthly to AS 1851.6-1997, AS 3666-1995

Air Pressurisation systems

BCA E 2.2, E1.8, AS1668.1-1998

Monthly to AS 1851.6-1983 or Monthly to AS 1851.6-1997, AS 3666-1995

Commercial Kitchen Exhaust

BCA F4.12, AS1668.2-1991

Monthly as per AS1851.6-1983

Emergency lifts

BCA E3.4, AS 1735.2-1997

BCA 90 Weekly to Occupational Health and Safety (Plant) Regulations 1995 BCA 96 Annual Inspections or in accordance with Manufacturers Specifications, the lesser of the two

Emergency lighting

BCA Part E4, AS 2293.1-1998

Every six months to AS 2293.2-1995

Emergency power supply

Electrical power supply BCA Spec G3.8

Every six months

Emergency warning and intercommunication systems

BCA E4.9, AS 2220.1-1989 & AS 2220.2-1989

Every three months to AS 1851.10-1989

Exit doors

BCA Section D

Every three months. Inspection to confirm exit doors are intact, operational and fitted with conforming hardware

Fire brigade connections

BCA 90Spec E1.7, Vic H101.9, Vic H103, AS 1670-1995 BCA 96 Spec E2.2a, Vic H103, AS1670-1995, AS2118.4-1995, AS2118.1-1999

Weekly to AS 1851.8-1987 or Weekly to AS 1851.8-1990

Fire control centres

BCA Spec E1.8

Annual Inspection

Fire control panels

(BCA 90 provisions) BCA Vic H101.9, AS1603.4-1987

Weekly to AS 1851.8-1987

Fire indicator panels

BCA Vic H 103.1, Practice Note No. 07

Weekly to AS 1851.8-1987

Fire curtains

BCA Spec H 1.3

Annual inspection for damage or deterioration

Fire dampers

BCA 90 AS 1682.2-1990 BCA 96 Part C3, AS 1668.2-1991

Annual inspection to AS 1851.6-1983

Fire detectors and alarm systems

BCA 90 Provision BCA E1.7, AS 1670-1995 BCA 96 Provisions BCA E2, AS 1670-1995

Weekly to AS 1851. 8-1987 Weekly to AS 1851.8-1987

Smoke and Heat Detectors

BCA Spec E2.2a, AS 1670-1995

Weekly to AS 1851.8-1987

Fire doors (including signs)

BCA Spec C3.4, AS 1905.1-1997

Monthly to AS 1851.7-1984

Fire extinguishers (portable)

BCA E1.6, AS 2444-1995

Every six months to AS 1851.1-1995

Fire hose reels

BCA E1.4, AS2441-1988

Every six months to AS 1851.2-1995

Fire hydrants

BCA E1.3, AS 2419.1-1994

Weekly to AS 1851.4-1992 where pumps are installed or monthly to AS1851.4-1992

Fire indices for materials

BCA C1.10, AS 1530.3-1999

Annual inspection to confirm no materials with potentially non-conforming fire indices occur

Fire isolated lift shafts

BCA Section C

Annual inspection

Fire isolated passageways

BCA Sections C and D

Annual inspection

Fire isolated ramps

BCA Sections C and D

Annual inspection

Fire isolated stairs

BCA Sections C and D

Annual inspection

Fire mains

BCA 90 provision only BCA Part E1, AS 2118.61995, AS 2419.1-1994

Weekly to AS 1851.4-1992

Fire protective coverings

BCA Section C

Annual inspection

Fire rated access panels

BCA Part C3

Annual inspection to AS 1851.7-1984 equivalent

Fire rated control joints

BCA Section C

Annual inspection

Fire rated materials applied to building elements

BCA Section C

Annual inspection

Fire resisting shafts

BCA Section C

Annual inspection

Fire resisting structures

BCA Section C

Annual inspection

Fire shutters

BCA Spec C3.4, AS 1905.2-1989

Annual inspection

Fire windows

BCA Spec C3.4

Annual inspection

Lightweight construction

BCA C1.8

Annual inspection

Mechanical ventilation systems

BCA E2.2, G3.8, Spec H1.3, AS 1668.2-1991

Monthly to AS 1851.6-1983, AS 3666.2-1995

Occupant warning systems

BCA 96 Spec E2.2a, BCA 90 Spec E1.7

Monthly to AS 1851.8 - 1990

Paths of travel to exits

BCA Section D

Every three months inspection to confirm travel paths are intact

Path of travel to road

BCA Section D

Every three months inspections to confirm path of travel is clear

Penetrations in fire-rated structures

BCA Part C3

Annual inspection

Smoke alarms

BCA 90 E1.7, G3.8, Vic H101.9, Vic H103 BCA 96 E1.7, G3.8 Vic H 103

Monthly to AS 1851.8-1987 (as applicable)

Smoke control measures

BCA Part E2, G3.8, Part H1

Monthly to AS 1851.6-1983

Smoke doors

BCA 90 C2.5, BCA Spec C3.4

Monthly to AS 1851.7-1984 or equivalent

Smoke/Heat vents

BCA 90E2.4, G3.8, AS 2665-1983 BCA 96 Spec E2.2c, Spec G3.8, AS2665-1983

Every six months to AS 1851.5-1981

Sprinkler systems

BCA 90, E1.5, AS 2118.1-1999, AS 2118.6-1995, Code of practice for installation of residential life safety sprinkler systems BCA 96, E1.5, C2.3, Vic H103, Reg. 5.15, AS2118.1-1999, AS 2118.4-1995, AS 2118.6-1995

Weekly to AS 1851.3-1985 or Weekly to AS 1851.3-1997

Stairwell pressurisation systems

BCA E2.2, AS 1668.1-1998

Monthly to AS 1851.6-1983

Static water storage

BCA Part E1, AS 2118.1-1999, AS 2118.6-1995, AS 2419.1-1994

Annual inspection

Vehicular access for large isolated buildings

BCA C2.4

Annual inspection to confirm access is maintained

Warning systems associated with lifts (including signs)

BCA Part E3

Annual inspection

 

WHAT IS THE DIFFERENCE BETWEEN THE OLD AND THE NEW ESSENTIAL SAFETY MEASURE TABLES?

The following Table shows how Table 1 (previous ESM items) and Table 2 (current ESM items) compare. It shows that the items are still relevant however have been separated or grouped in different ways. Benchmark will generally elect to use the current list (Table 1) to conduct the Audits.

 TABLE 3: Source Table Comparison- Schedule of Essential Safety Measures

2004 LIST   1994 LIST

Table I1.1

 

 

ESSENTIAL SAFETY MEASURES - BUILDING FIRE INTEGRITY

 

 

Essential safety measure

 

 

Building elements required to satisfy prescribed fire resistance levels

 

Fire resisting structures

 

Fire resisting shafts

 

Fire isolated lift shafts

 

 

Materials and assemblies required to satisfy prescribed fire hazard properties

  Fire indices for materials
Elements required to be non-combustible, provide fire protection, compartmentation or separation

 

Lightweight construction

 

Fire protective coverings

 

Fire rated materials applied to building elements

Wall-wetting sprinklers (including doors and windows required in conjunction with wall-wetting sprinklers)

 

 

Fire doors (including sliding fire doors and their associated warning systems) and associated self-closing, automatic closing and latching mechanisms

 

Fire doors (including signs)

 

 

Fire rated access panels

Fire windows (including windows that are automatic or permanently fixed in the closed position)

 

Fire windows

Fire shutters

 

Fire shutters

Solid core doors and associated self-closing, automatic closing and latching mechanisms

 

 

Fire-protection at service penetrations through elements required to be fire-resisting with respect to integrity or insulation, or to have a resistance to the incipient spread of fire

 

Penetrations in fire-rated structures

Fire protection associated with construction joints, spaces and the like in and between building elements required to be fire-resisting with respect to integrity and insulation

 

Fire rated control joints

Smoke doors and associated self-closing, automatic closing and latching mechanisms

 

Smoke doors

Proscenium walls (Fire Curtains)

 

Fire curtains

 

 

 

Table I1.2

 

 

ESSENTIAL SAFETY MEASURES - MEANS OF EGRESS

 

 

Essential safety measure

 

 

Paths of travel to exits

 

Paths of travel to exits

Discharge from exits (including paths of travel from open spaces to the public roads to which they are connected)

 

Path of travel to road

Exits (including fire-isolated stairways and ramps, non-fire isolated stairways and ramps, stair treads, balustrades and handrails associated with exits, and fir-isolated passageways)

 

Exit doors

 

Fire isolated passageways

 

Fire isolated ramps

 

Fire isolated stairs

Smoke lobbies to fire-isolated exits

 

Lightweight construction

Open access ramps or balconies for fire-isolated exits

 

Exit doors

 

Path of travel to road

Doors (other than fire or smoke doors) in a required exit, forming part of a required exit or in a path of travel to a required exit, and associated self-closing, automatic closing and latching mechanisms

 

Exit doors

 

 

 

Table I1.3

 

 

ESSENTIAL SAFETY MEASURES - SIGNS

 

 

Essential safety measure

 

 

Exit signs (including direction signs)

 

Exit signs

Signs warning against the use of lifts in the event of fire

 

Warning systems associated with lifts (including signs)

Warning signs on sliding fire doors and doors to non-required stairways, ramps and escalators

 

Fire doors (including signs)

Signs, intercommunication systems, or alarm systems on doors of fire-isolated exits stating that re-entry to storey is available

 

Exit doors

Signs alerting persons that the operation of doors must not be impaired

 

Exit doors

Signs required on doors, in alpine areas, alerting people that they open inwards

 

Exit doors

Fire order notices required in alpine areas

 

Exit doors

 

 

 

Table I1.4

 

 

ESSENTIAL SAFETY MEASURES - LIGHTING

 

 

Essential safety measure

 

 

Emergency lighting

 

Emergency lighting

 

 

 

Table I1.5

 

 

ESSENTIAL SAFETY MEASURES - FIRE FIGHTING SERVICES AND EQUIPMENT

 

 

Essential safety measure

 

 

Fire hydrant system (including on-site pump set and fire-service booster connection)

 

Fire hydrants

 

 

Fire mains

Fire hose reel system

 

Fire hose reels

Sprinkler system

 

Sprinkler systems

 

 

Static water storage

Portable fire extinguishers

 

Fire extinguishers (portable)

Fire control centres (or rooms)

 

Fire control centres

Provisions for special hazards

 

 

 

 

 

Table I1.6

 

 

ESSENTIAL SAFETY MEASURES - AIR HANDLING SYSTEMS

 

 

Essential safety measure

 

 

Smoke hazard management systems:
•   automatic air pressurisation systems for fire- isolated exits
•   zone smoke control system
•   smoke exhaust system automatic smoke and heat vents (including automatic vents for atriums)
•   air handling systems that do not form part of a smoke hazard management system and which may unduly contribute to the spread of smoke
•    miscellaneous air- handling systems covered by Sections 5 and 11 of AS/NZS1668.1 serving more than one fire compartment

 

Air Pressurisation systems

 

Commercial Kitchen Exhaust

 

Fire dampers

 

Smoke/Heat vents

 

Stairwell pressurisation systems

Carpark mechanical ventilation system

 

Mechanical ventilation systems

Atrium smoke control system (see above for smoke and heat vents)

 

Smoke control measures

  

 

 

Table I1.7

 

 

ESSENTIAL SAFETY MEASURES - AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS

 

 

Essential safety measure

 

 

Smoke and heat alarm system

 

Smoke alarms

Smoke and heat detection system

 

Fire brigade connections

 

 

Fire control panels

 

 

Fire indicator panels

 

 

Fire detectors and alarm systems

 

 

Smoke and Heat Detectors

Atrium fire detection and alarm systems

 

Fire detectors and alarm systems

 

 

 

Table I1.8

 

 

ESSENTIAL SAFETY MEASURES - OCCUPANT WARNING SYSTEMS

 

 

Essential safety measure

 

 

Emergency warning and intercommunication system

 

Emergency warning and intercommunication systems

Building occupant warning system

 

Occupant warning systems

 

 

 

Table I1.9

 

 

ESSENTIAL SAFETY MEASURES - LIFTS

 

 

Essential safety measure

 

 

Stretcher facilities in lifts

 

 

Emergency lifts

 

Emergency lifts

Passenger lift fire service controls

 

 

 

 

 

Table I1.10

 

 

ESSENTIAL SAFETY MEASURES - STANDBY POWER SUPPLY SYSTEMS

 

 

Essential safety measure

 

 

Standby power supply system

 

Emergency power supply

 

 

 

Table I1.11

 

 

ESSENTIAL SAFETY MEASURES - BUILDING CLEARANCE AND FIRE APPLIANCES

 

 

Essential safety measure

 

 

Open space around large isolated buildings

 

Vehicular access for large isolated buildings

Vehicular access around large isolated buildings

 

Vehicular access for large isolated buildings

 

 

 

 

 

 

ESSENTIAL SAFETY MEASURES - MECHANICAL VENTILATION

 

 

Essential safety measure

 

 

Air conditioning systems

 

Air conditioning systems